Fire Door Hardware: A Complete Compliance Guide
So you’ve installed the fire-rated doors. Check. But here’s a critical detail many people miss: the door itself is only half the equation. Every single piece of fire door hardw…
Get a Free Fire Door Quote for Your NYC Property
Fill out the form below or call us at (718) 455-8442 — we respond fast.
So you’ve installed the fire-rated doors. Check. But here’s a critical detail many people miss: the door itself is only half the equation. Every single piece of fire door hardware, from the hinges to the latch, must also meet its own strict code requirements. Using just one non-compliant component can invalidate the entire fire door assembly. This isn't just about passing an inspection—it's a crucial safety measure that protects people and property. We'll cover exactly what you need to know to get it right.
This guide explains what hardware is required on fire rated doors, what the codes actually mandate, and how to select components that will pass inspection the first time.
Need compliant fire rated door hardware specified and installed for your NYC project? Request a free site estimate from Universal Fire Doors.
How Hardware Impacts Your Fire Door Rating
A fire door assembly is rated as a complete system, not as individual parts. The Underwriters Laboratories (UL) listing for a fire door covers the door, the frame, and the hardware used with it. If you swap in hardware that was not tested as part of a listed assembly, you void the certification.
NFPA 80, the National Fire Protection Association's standard for fire doors and windows, is the governing document for fire door assemblies in New York City and most of the country. It specifies which hardware types are required, how they must function, and what certification marks they must carry. Inspectors check hardware during the annual fire door inspection cycle. Non-compliant hardware generates violations that require replacement before the building passes.
The key principle: every piece of hardware on a fire door must be either listed for use with that door assembly or specifically permitted by NFPA 80 for the door's rating category. When in doubt, ask your manufacturer for documentation.
What Fire Door Hardware Is Required by Code?
The following components are required on most fire rated door assemblies. Some requirements vary based on the door's fire rating (20, 45, 60, 90 minutes, or 3 hours), the building type, and the occupancy classification.
Getting Hinges and Pivots Right
Fire rated doors require hinges that are specifically listed for fire door use. Standard residential ball-bearing hinges are not acceptable. Listed fire door hinges are manufactured from steel (not brass or aluminum), carry a UL mark, and are sized to the door weight and height.
NFPA 80 requires a minimum of three hinges on doors up to 90 inches in height, with additional hinges for taller doors. Stainless steel hinges are permitted where corrosion resistance is needed, provided they carry the appropriate fire rating listing.
Meeting High-Temperature Requirements
It’s not enough for a hinge to simply swing a door. During a fire, every piece of hardware on a fire door must endure extreme heat without melting, warping, or failing. This is why all hardware, from hinges and locks to latches and closers, must be specifically fire-rated. These components are tested alongside the door itself to ensure they can perform their function for the entire duration of the door's fire rating, whether it's 20 minutes or 3 hours. Using hardware that isn't certified for high temperatures means it could fail when needed most, allowing fire and smoke to spread and compromising the safety of the entire building. This is why selecting the correct fire-rated doors and hardware assembly is so critical for compliance and safety.
Why Latching Hardware Is Critical
All fire rated doors must positively latch when closed. A self-closing door that swings shut but does not latch is not code-compliant, regardless of how good the closer is. The latch must engage the strike plate automatically; deadbolts and manual latches do not satisfy this requirement on their own.
For panic hardware and exit devices, NFPA 80 requires that they latch automatically when the door closes. Rim-mounted and vertical rod devices are common in commercial occupancies. Mortise locksets work well in corridors and stairwells where a fire door also serves as a lockable security door.
How Door Closers Keep You Safe
Every fire rated door must have a listed self-closing device. This is one of the most critical requirements: an open fire door provides zero protection. The door closer must be strong enough to close and latch the door reliably from any open position, including against positive air pressure from an HVAC system.
Closers must be listed by UL or another recognized testing laboratory for fire door use. The closer arm and mounting bracket must also be listed. Surface-mounted closers, concealed overhead closers, and floor-spring closers are all available in listed configurations.
For compliance purposes, closer spring tension must be set at the minimum force needed to close and latch the door. Door closers that fail to close the door from any position are cited during annual inspections.
Managing Double Doors with Coordinators
When a fire door opening has two active door leaves with overlapping astragals, a door coordinator is required to ensure the leaves close in the correct sequence. If the wrong leaf closes first, the astragal prevents the second leaf from latching. Coordinators are available as surface-mounted overhead devices and as integrated components within the closer.
Stopping Smoke with Seals and Door Bottoms
Depending on the door's fire rating and whether it is also required to control smoke migration, the assembly may need to include smoke seals at the head, jamb, and meeting edges, plus an automatic door bottom. NYC's 2022 fire code includes smoke and draft control requirements that go beyond simple fire rating in specific occupancy types.
Automatic door bottoms drop a seal when the door closes, eliminating the gap at the floor that would otherwise allow smoke to pass. These devices must be listed for fire door use; non-rated automatic door bottoms are not acceptable substitutes.
What Are Astragals and Why Do You Need Them?
On pairs of fire rated doors, an astragal covers the gap between the two leaves. Some fire door assemblies use overlapping astragals (where one leaf overlaps the other), while others use independent astragals mounted to each leaf. The specific requirement depends on the door's fire rating period. Doors rated at 90 minutes and above generally require a more substantial overlapping astragal than 20-minute doors.
Not sure which hardware your building's fire doors require? Schedule a free site evaluation with Universal Fire Doors and get a complete compliance assessment.
Maintaining Proper Door Clearances
Even with all the right hardware, a fire door can fail inspection if the gaps around it are too large. The space between the door and the frame, known as the clearance, is critical for preventing smoke and flames from passing through. According to NFPA 80, these clearances must be minimal, typically no more than 1/8 inch at the jambs, head, and meeting stiles, and no more than 3/4 inch at the bottom (undercut). An oversized gap can render the entire assembly non-compliant. During an annual inspection, this is one of the first things an inspector will measure. If you can see a lot of light streaming through the cracks around your closed fire doors, it’s a sign that you may have a compliance issue that needs professional adjustment or repair. Ensuring these gaps are within tolerance is a key part of maintaining your building's fire safety system.
Additional Fire-Rated Hardware Components
Beyond the essential hinges, latches, and closers, many fire doors include other hardware to meet specific functional needs. These components are not required on every fire door, but when they are used, they must also be fire-rated and installed correctly so they don't compromise the integrity of the assembly. This includes items that allow for visibility, protect the door surface, or provide other conveniences. For example, small windows, known as vision panels, are common in hospital and school environments. Similarly, kick plates are often added to protect the bottom of a door in high-traffic areas. Each of these additions must be listed for use on a fire-rated assembly and installed in a way that maintains the door's certification.
Vision Panels (Windows)
You can absolutely have a window in a fire door, but it can’t be just any piece of glass. These small windows, called vision panels or vision lites, are made from special fire-rated glazing that has been tested to withstand high temperatures for a specific duration. The size of the vision panel is strictly limited by the door's overall fire rating—a 90-minute door will have different glass size limitations than a 20-minute door. These are essential in locations like classroom doors, where seeing into a hallway is a matter of safety and convenience, but they must be factory-installed or prepared by a certified shop to ensure compliance.
Kick Plates and Letter Boxes
Adding accessories like kick plates, armor plates, or even letter boxes to a fire door requires careful consideration. You can't simply drill holes and mount them, as any unauthorized penetration of the door's surface can void its fire rating. These items must be specifically listed for use on fire doors and installed according to the manufacturer's instructions and NFPA 80 standards. For example, kick plates are typically applied with adhesive or attached with through-bolts in pre-approved locations. Any modification must be done in a way that doesn't compromise the door's structural integrity, ensuring it still performs as expected in a fire. When in doubt, it's always best to have certified professionals handle the installation.
How to Read Fire Door Hardware Ratings
Hardware ratings and door ratings are related but not identical. Here is what you need to know:
- Fire door rating periods: Doors are rated at 20, 45, 60, 90, or 180 minutes (3 hours). The rating reflects how long the assembly can withstand a fire test without failing.
- Hardware listing: Hardware is listed by a testing lab (most commonly UL) for use in specific fire door rating categories. Not all hardware listed for a 20-minute door is appropriate for a 90-minute door.
- Match hardware to door rating: Always specify hardware that is listed for the fire rating of your door assembly, or higher. Hardware listed only for 20-minute assemblies cannot be installed on a 90-minute door.
- Labeling: Look for a permanent label on the hardware identifying the manufacturer, the UL file number, and the listing category. Surface-mounted hardware carries this label on the body; hinges typically carry it on the hinge leaf.
For a detailed breakdown of fire rating periods and what each one means for your building, see our guide to fire door ratings explained.
Beyond UL: Other Certification Labels to Look For
While Underwriters Laboratories (UL) is the most familiar name you'll see, it's not the only one. Other certified testing labs, like Intertek (which uses the Warnock Hersey mark) and FM Approvals, also test and list fire door hardware. What matters most isn't the specific lab, but the presence of a permanent certification label. This label is your proof that the hardware meets stringent safety standards. It should clearly identify the manufacturer and the specific listing category it's approved for. Remember, every component, from the hinges to the closer, must be certified for the door's specific fire rating. You can't use hardware listed for a 20-minute door on a 90-minute assembly. Ensuring all your fire-rated doors have correctly certified hardware is essential for passing inspections and maintaining safety.
The Risks of Non-Compliant Fire Door Hardware
Using the wrong hardware isn't just a minor code violation; it introduces serious risks that can have devastating consequences for your building and its occupants. A fire door assembly is a life-safety system, and every component must function correctly to provide protection. When hardware fails, is incorrect, or is tampered with, the entire system is compromised. This can lead to accelerated fire spread, increased property damage, and significant legal and financial liability. Understanding these risks is the first step toward ensuring your building is truly safe and compliant with NYC fire codes, protecting both your property and the people inside it.
Think of it this way: a fire door with non-compliant hardware is like a seatbelt that doesn't buckle. It might look the part, but it will fail when you need it most. From hinges that can't withstand high temperatures to closers that don't fully latch the door, each incorrect component creates a weak point in your building's fire defense. During an annual inspection, these issues will result in violations that must be corrected. More importantly, in a real fire, these failures can mean the difference between a contained incident and a full-blown disaster, making hardware compliance a non-negotiable aspect of building safety.
The "Chimney Effect": How Propped Doors Fuel Fires
A fire door’s main job is to compartmentalize a building, containing fire and smoke to a specific area and slowing their spread. Wedging a fire door open completely negates this function. When a door is left open, it creates a pathway for oxygen to feed the flames and for smoke to travel freely. This can produce a dangerous "chimney effect," pulling fire and toxic smoke rapidly through corridors, stairwells, and between floors. What could have been a small, contained fire can quickly become a building-wide catastrophe, all because a single door failed to close and do its job.
Insurance and Liability Concerns
Beyond the immediate danger to life, non-compliant fire door hardware creates significant financial and legal liabilities for building owners. In the aftermath of a fire, investigators will scrutinize the building's safety systems. If they discover that a fire door was propped open or fitted with improper hardware, your insurance provider may have grounds to deny your claim for the resulting damages. This leaves you responsible for the full cost of repairs and exposes you to potential lawsuits from tenants or anyone harmed by the fire's spread, turning a tragic event into a financial disaster.
Why Convenience Can't Compromise Safety
One of the most common but critical compliance failures involves latching. Many people assume that as long as a door closer swings the door shut, it’s doing its job. However, a fire door must positively latch into the frame automatically to be compliant. A door that closes but doesn’t securely latch offers little resistance to the intense pressures created by a fire. Manual deadbolts or latches that require someone to turn a key or knob do not meet this standard for fire safety. The hardware must be designed to engage the strike plate on its own, every time, ensuring the door remains a solid barrier against fire and smoke.
Top Fire Door Hardware Mistakes to Avoid
Annual fire door inspections in New York City generate violations across several recurring hardware categories. Knowing what inspectors look for helps building owners and contractors get ahead of the problem.
When Your Door Closer Doesn't Latch
This is the most frequent hardware violation. The closer may be listed and properly installed, but if the spring tension has been reduced to make the door easier to open, the door may not latch reliably. Closers must be set at a minimum force sufficient to close and latch the door from any open position. Adjusting closer spring tension is a maintenance item, not a hardware replacement, but it must be done correctly.
The Dangers of Using Non-Listed Hardware
Many buildings have had hardware replaced over the years with whatever was on the supply house shelf. Standard commercial hardware is often not listed for fire door use. Inspectors identify non-listed hardware by the absence of a UL label or an incorrect listing category for the door's rating period.
Why You Should Never Block or Remove a Closer
Wedges, door stops, and magnetic hold-opens (without a listed fire alarm release) are all violations. NYC's self-closing door law makes it illegal to prop open a fire door in multi-family buildings. Repeated inspections since the law was strengthened in 2019 have generated thousands of violations. Listed electromagnetic hold-open devices that release on fire alarm activation are the only compliant option for doors that must be held open during normal operations.
The Problem with Damaged Astragals and Seals
Worn, torn, or missing astragals and seals are cited regularly. These components are subject to daily wear and have finite service lives. Building maintenance programs should include periodic inspection of seals and astragals, not just closers and latches.
Spotting Coordinator Failures on Double Doors
Coordinators seize or wear out over time. When a coordinator fails, the door leaves no longer close in the correct sequence, and the second leaf cannot latch. This is both a compliance violation and an immediate safety concern. Coordinators are often overlooked in maintenance programs because they are smaller and less visible than closers.
Overlooking Training and Budgeting for Maintenance
Fire door compliance isn't a one-time setup; it's an ongoing commitment. A common pitfall for building managers is failing to budget for routine maintenance and staff training. When a component fails, the immediate goal is a quick fix, which can lead to grabbing non-listed hardware from a local supplier. While this might solve the immediate problem, it creates a new one: a compliance violation waiting to happen during the next inspection. Proactively budgeting for maintenance ensures you have the resources to use correct, listed hardware for every repair. It also means your maintenance team needs the right training. Tasks like adjusting door closer tension seem simple, but doing it incorrectly can cause the door to fail its next inspection. Investing in proper door repair and maintenance services or training your staff is a critical step in avoiding costly fines and ensuring your building remains safe.
How to Choose Compliant Fire Door Hardware
Choosing the right hardware for a fire rated door is not complicated, but it requires discipline. Follow these steps to avoid costly replacements after installation:
- Start with the door rating. Confirm the fire rating of the door assembly before specifying any hardware. The door label will show the rating period (20, 45, 60, 90, or 180 minutes).
- Verify hardware listing. Every component must carry a UL or equivalent listing for that rating category. Request the UL file number from the supplier and verify it at ul.com/database before ordering.
- Check NFPA 80 requirements for your occupancy. Some occupancy types (health care, educational) carry additional hardware requirements beyond the base fire code. Work with your architect or code consultant to identify which sections of NFPA 80 apply.
- Buy from the same product family where possible. Door hardware manufacturers publish listing data at the product family level. Mixing components from different manufacturers can create listing gaps that are difficult to document during an inspection.
- Keep documentation. Retain the UL certification sheets and product data sheets for all hardware installed. Inspectors may ask for documentation, and it significantly shortens the process when violations need to be disputed or resolved quickly.
- Plan for maintenance from day one. Listed hardware is only compliant as long as it functions as tested. Factor in annual lubrication of hinges and closers, spring tension checks, and seal inspections as part of your building maintenance program.
For ongoing maintenance requirements, see our complete guide to fire door maintenance and testing requirements.
Defining Roles: Architects, Engineers, and Contractors
Getting fire door hardware right is a team sport, with each player having a distinct and critical role. Architects are the initial planners; they design the building's flow and select hardware that meets local codes while fitting the overall vision. Engineers then step in to verify the technical specifications, ensuring the chosen hardware is compatible with the door, frame, and building structure. Finally, the contractor brings the plan to life. This is where precision is paramount. A skilled contractor, like the OSHA-certified crews at Universal Fire Doors, must install every component exactly according to the manufacturer's instructions. When architects, engineers, and contractors communicate and collaborate effectively, the result is a fire door assembly that is safe, compliant, and built to last.
Beyond the Code: Factoring in Security and Aesthetics
While meeting fire code is non-negotiable, it’s not the only factor to consider. Fire doors are often part of a building's primary security system. The locks and latching hardware must be robust enough to prevent unauthorized entry while still allowing for quick egress in an emergency. This dual function is especially important for apartment and hotel room doors. Furthermore, the hardware needs to look good. An institutional-style panic bar might be fine for a back-of-house emergency exit, but it would look out of place on a sleek commercial hollow metal door in an office lobby. Thankfully, manufacturers offer a wide range of finishes and designs, allowing you to choose hardware that complements your building’s aesthetic without compromising on safety or compliance.
Can You Use Panic Bars on Fire Doors?
Egress doors in assembly occupancies, educational buildings, and other high-occupancy spaces are required to have panic hardware (also called exit devices). When these doors are also fire rated, the panic hardware must be listed for both purposes.
Listed panic hardware for fire doors must:
- Release the latch with a horizontal push force of 15 pounds or less
- Latch automatically when the door closes, with no manual action required
- Be tested and listed for the fire rating period of the door assembly
- Not include through-bolt fasteners that create a thermal bridge through the door face (certain configurations are not permitted on higher-rated assemblies)
Rim-mounted exit devices, mortise exit devices, and vertical rod exit devices are all available in fire-rated configurations. The selection depends on the door construction, the frame type, and whether the door is a single or pair. See our in-depth guides on panic bar installation and double door panic bar installation for detailed installation guidance.
Working on an NYC project that requires listed panic hardware on fire rated doors? Contact Universal Fire Doors for product specification and compliant installation.
Understanding the Difference: Panic vs. Fire Exit Hardware
While many people use the terms "panic bar" and "fire exit hardware" interchangeably, they are not the same thing in the eyes of a fire inspector. Standard panic hardware is designed for one primary purpose: fast egress. It's built for high-traffic areas where a large number of people might need to exit quickly. However, it is not typically built to withstand the intense heat of a fire. Fire exit hardware, on the other hand, is a special category of panic hardware. It has been tested and listed not only for panic egress but also for its ability to perform during a fire. Using a standard, non-rated panic bar on a fire-rated door will void the door's certification and result in a compliance violation.
The "No Dogging" Rule for Fire Doors
One of the most significant differences between standard panic hardware and fire exit hardware is a feature called "dogging." On a regular panic bar, a dogging device allows you to retract the latch bolt, essentially putting the door in a push/pull mode without it latching shut. This is common in commercial buildings to reduce noise and wear during business hours. However, this feature is strictly prohibited on fire doors. A fire door must be able to positively latch every single time it closes to effectively contain smoke and flames. Because of this, true fire exit hardware is manufactured without a mechanical dogging mechanism, ensuring it can never be left in an unlatched state and is always ready to perform its life-saving function.
Installation Requirements: Height and Width
Proper installation is just as critical as selecting the right device. The push pad of the panic bar must cover at least half the width of the door, ensuring it can be easily activated in an emergency, even in a crowd. It must also be installed at a specific height—typically between 34 and 48 inches above the finished floor—to comply with accessibility standards. Beyond the physical placement, performance is key. The device must unlatch with 15 pounds of force or less, making it easy for anyone to operate. As we've covered, it must also latch automatically when the door closes. These precise requirements are why professional installation is essential, especially in high-occupancy buildings like hospitals and schools.
Frequently Asked Questions About Fire Rated Door Hardware
Can I use any door closer on a fire rated door?
No. The door closer must be listed by a recognized testing laboratory (such as UL) for use on fire rated doors, and it must be listed for the specific fire rating period of your door. A closer not listed for fire door use or listed only for a lower rating period is not compliant. Look for the UL listing label on the closer body and verify the listing category matches your door's rating.
What happens if I install non-listed hardware on a fire door?
Installing non-listed hardware voids the door's UL listing and renders the entire fire door assembly non-compliant. In NYC, this will result in a violation during the annual fire door inspection. The building owner will be required to replace the hardware with listed components and document the correction. Repeated or uncorrected violations can result in fines and, in severe cases, occupancy restrictions.
Do all fire doors need smoke seals?
Not all fire rated doors require smoke seals, but many do. NFPA 80 and the International Building Code specify when smoke and draft control seals are required based on the opening's location, the occupancy type, and the fire rating period. In general, doors in smoke compartment barriers and certain corridor locations require smoke seals. Consult NFPA 80 and the applicable building code section for your specific project.
How often do fire door closers need to be replaced?
Listed fire door closers do not have a fixed service life, but they do wear out. NFPA 80 requires annual inspection and testing of all fire door assemblies, including closers. A closer that fails to reliably close and latch the door from any open position must be repaired or replaced immediately. Proactive lubrication and adjustment can extend service life, but once a closer fails the annual test, replacement is required before the building passes inspection.
Can I install a standard commercial hinge on a fire rated door?
No. Standard commercial hinges that are not listed for fire door use are not permitted on fire rated doors. Listed fire door hinges are made from steel (not brass or aluminum), carry a UL mark for fire door use, and are sized for the door weight and height. Three hinges minimum are required for doors up to 90 inches tall. Always verify the hinge listing before installation.
Partnering with an Expert on Fire Door Codes
Selecting and installing compliant fire door hardware is not a task for guesswork. Universal Fire Doors provides an NYC door hardware installation service for compliant closers, hinges, latches, locks, panic hardware, and exit devices. The combination of NFPA 80 requirements, NYC fire code, and building-specific occupancy requirements creates a set of intersecting rules that must all be satisfied simultaneously.
Universal Fire Doors has been manufacturing and installing fire rated door assemblies in New York City since 1924, including fire-rated door installation and replacement services for buildings that need a complete rated assembly. As a Steel Door Institute (SDI) registered manufacturer, every door and frame we produce is built to comply with applicable code requirements. We specify and supply listed hardware as part of complete door assembly packages, so contractors and building owners get a single, documented solution that holds up under inspection.
From single replacement doors to large multi-floor renovation projects, our team handles specification, manufacturing, delivery, and installation. We carry UL fire ratings from 20 minutes through 3 hours and can supply matching hardware for each rating category.
Learn more about what makes a fire door and the full range of options available for commercial buildings. When you're ready to move forward, request a free site estimate and we'll walk through the requirements for your specific project.
Key Takeaways
- Treat it as an all-or-nothing system: A fire door's rating applies to the entire assembly, so the door, frame, and every piece of hardware must be certified to work together. Using a single non-rated component, like a hinge or lock, voids the door's certification and makes it unsafe.
- Closing isn't enough; it must latch: For a fire door to be compliant, it needs a listed closer that swings it fully shut and a latch that automatically secures it in the frame. A door that closes but doesn't positively latch fails its primary job of containing fire and smoke.
- Small hardware mistakes have big consequences: Seemingly minor issues, such as using the wrong hinges, propping a door open, or installing a standard panic bar, will result in failed inspections and create serious safety risks. Always verify hardware is certified and installed correctly to avoid fines and liability.
Related Articles
Ready to Get Started?
NYC's trusted commercial fire door specialists — fast response, code-compliant work.
What NYC Property Owners Say
UFD replaced 40 fire doors in our office tower on schedule. Their team knew every code requirement and coordinated around our tenants seamlessly.
— Robert M. — Property Manager, Midtown Manhattan
Called them for an emergency repair after a failed inspection. They were on-site within hours and got us back to compliance the same day.
— Angela T. — Facilities Director, Brooklyn Medical
Transparent pricing, expert crew, and the documentation they provided for our building file was perfect. Best contractor experience in NYC.
— James W. — Building Owner, Queens
Frequently Asked Questions
How Hardware Impacts Your Fire Door Rating
A fire door assembly is rated as a complete system, not as individual parts. The Underwriters Laboratories (UL) listing for a fire door covers the door, the frame, and the hardware used with it. If yo…
What Fire Door Hardware Is Required by Code?
The following components are required on most fire rated door assemblies. Some requirements vary based on the door's fire rating (20, 45, 60, 90 minutes, or 3 hours), the building type, and the occupa…
How to Read Fire Door Hardware Ratings
Hardware ratings and door ratings are related but not identical. Here is what you need to know:
The Risks of Non-Compliant Fire Door Hardware
Using the wrong hardware isn't just a minor code violation; it introduces serious risks that can have devastating consequences for your building and its occupants. A fire door assembly is a life-safet…
Top Fire Door Hardware Mistakes to Avoid
Annual fire door inspections in New York City generate violations across several recurring hardware categories. Knowing what inspectors look for helps building owners and contractors get ahead of the …
Emergency Fire Door Service — NYC 24/7
Failed inspection? Damaged door? We respond across all five boroughs.
📞 Call (718) 455-8442Need fire door help in NYC?
We manufacture & install in 3–5 days. Violations, replacements & inspections across all 5 boroughs.
Get a Free Estimate →📞 (718) 455-8442Mon–Fri 8AM–4:30PM · No obligationWhy Universal Fireproof Door
- ✓ Manufacturing in Brooklyn since 1924
- ✓ UL Listed & NYC MEA Approved
- ✓ Our own crews — no subcontractors
- ✓ Serving all 5 NYC boroughs & Long Island